AIR FILTERS

CLEAN AIR FOR HIGH TECHNOLOGIES

decor

W-shaped filters (FCW Series)

View:
Filtration class:
Width, mm:
Height, mm:
Depth, mm:
Filter surface area, m²:
Nominal capacity, m³/h:
DOWNLOAD CATALOG
Filtration of supply and exhaust air is necessary to clean it from macro and micro contaminants of various nature: sand, dust, aerosol suspensions, odors, smoke, steam, toxic gases, infectious and radioactive particles, etc.
A simple panel air filter consists of a cut of filter media fixed with a grid. The filter element is in turn fastened with a metal U-shaped frame profile. Panel filters are placed at the air intake for basic air cleaning from large contaminants.
A cassette filter with panel construction is an upgraded panel filter. The filter media in a cassette filter is "crumpled" into a fold (pleated) and fixed on a pleated support grid. The pleated filter element is placed in a metal U-shaped or rigid rectangular frame.
The filter element of such designs is represented by a voluminous non-woven material sewn in the form of pocket bags fixed in a rigid frame on crossbars. The greater the number and depth of pockets, the larger the filter surface area and the longer the product's service life. Depending on the type of filter media used, pocket filters are suitable for the first and second stages of air purification.
In compact W-type filters, a pleated filter pack is installed in the housing at an angle to the airflow in the form of W-shaped zigzags. The W-shape of the filter element is fixed by a reinforced grid. The filter pack itself is placed in a lightweight, impact-resistant, moisture-resistant polymer housing. The pleating and compact arrangement of the filter element significantly increases the effective area of the filter media. This increases dust holding capacity, and therefore the duration of the product's operation.
HEPA (High Efficiency Particle Absorption) filters are highly efficient devices for final ultra-fine air purification that has undergone preliminary (coarse and fine) treatment. The mechanism of capturing contaminating microparticles in HEPA filters is fundamentally different from others and is due to the adhesive properties of the filter fiber. A HEPA cartridge is a filter pack made of ultra-thin corrugated separated glass paper hermetically mounted in the housing profile.
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X490X420
W-shaped compact filter, 592x490x420 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 490
Height, mm 592
Depth, mm 420
Filter surface
area, m²
20.2
Nominal
capacity,
m³/h
2800
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X592X420
W-shaped compact filter, 592x592x420 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 592
Height, mm 592
Depth, mm 420
Filter surface
area, m²
25.0
Nominal
capacity,
m³/h
3400
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X287X292
W-shaped compact filter, 592x287x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 287
Height, mm 592
Depth, mm 292
Filter surface
area, m²
7.8
Nominal
capacity,
m³/h
1700
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X490X292
W-shaped compact filter, 592x490x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 490
Height, mm 592
Depth, mm 292
Filter surface
area, m²
14.0
Nominal
capacity,
m³/h
2800
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X592X292
W-shaped compact filter, 592x592x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 592
Height, mm 592
Depth, mm 292
Filter surface
area, m²
16
Nominal
capacity,
m³/h
3400
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X287X420
W-shaped compact filter, 592x287x420 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 287
Height, mm 592
Depth, mm 420
Filter surface
area, m²
12.5
Nominal
capacity,
m³/h
1700
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X490X420
W-shaped compact filter, 592x490x420 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 490
Height, mm 593
Depth, mm 420
Filter surface
area, m²
22.5
Nominal
capacity,
m³/h
2800
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X592X420
W-shaped compact filter, 592x592x420 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 592
Height, mm 592
Depth, mm 420
Filter surface
area, m²
8.0
Nominal
capacity,
m³/h
3400
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X287X292
W-shaped compact filter, 592x287x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 287
Height, mm 592
Depth, mm 292
Filter surface
area, m²
8.5
Nominal
capacity,
m³/h
1700
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X490X292
W-shaped compact filter, 592x490x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 490
Height, mm 592
Depth, mm 292
Filter surface
area, m²
15
Nominal
capacity,
m³/h
2800
69e5515d900e542d15302a1b19edf8ef
W-SHAPED COMPACT FILTER (FCW SERIES), 592X592X292
W-shaped compact filter, 592x592x292 mm
Filtration class M6, F7, F8, F9, E10, E11, E12, H13, H14
Width, mm 592
Height, mm 592
Depth, mm 292
Filter surface
area, m²
19
Nominal
capacity,
m³/h
3400

ORDER FORM

images





    INFORMATION

    Compact W-type filters for fine filtration are designed for effective air purification from fine aerosols in gas turbine and compressor installations, ventilation and air conditioning systems. They can also be used as pre-filters before high-efficiency HEPA and ULPA filters.

    Filter Construction

    The filter housing is made of impact-resistant polystyrene, inside which filter packs reinforced with protective grids are installed at an angle to the air flow. These are sealed around the perimeter with a special two-component polyurethane adhesive. A seamless foamed polyurethane applied by adhesion is used as a sealant.

    Filter Type Size (H x W x D), mm Number of filter packs, pcs. Filtration class Interstate Standard R EN 779-20141 Interstate Standard R EN 1822-1-20102 Nominal capacity, m3/h Initial pressure drop, Pa Filter surface area, m2 Weight, kg
    FCW;
    FCW-PLA-GT
    592х592х292 8 M6 3400 80 19 7,0
    F7 90
    F8 100
    F9 120
    E10 170
    E11 200
    E12 250
    H13 300
    H14 400
    FCW;
    FCW-PLA-GT
    592х490х292 8 M6 2800 80 15 5,9
    F7 90
    F8 100
    F9 120
    E10 170
    E11 200
    E12 250
    H13 300
    H14 400
    FCW;
    FCW-PLA-GT
    592х287х292 8 M6 1700 80 8,5 4,0
    F7 90
    F8 100
    F9 120
    E10 170
    E11 200
    E12 250
    H13 300
    H14 400
    FCW;
    FCW-PLA-GT
    592х592х420 8 M6 3400 50 28,0 12,0
    F7 60
    F8 80
    F9 95
    E10 140
    E11 160
    E12 210
    H13 260
    H14 360
    FCW;
    FCW-PLA-GT
    592х490х420 8 M6 2800 50 22,5 10
    F7 60
    F8 80
    F9 95
    E10 140
    E11 160
    E12 210
    H13 260
    H14 360
    FCW;
    FCW-PLA-GT
    592х287х420 8 M6 1700 50 12,5 7
    F7 60
    F8 80
    F9 95
    E10 140
    E11 160
    E12 210
    H13 260
    H14 360
    FCW;
    FCW-PLA-GT
    592х592х292 6 M6 3400 70 17,0 6,5
    F7 80
    F8 90
    F9 110
    E10 160
    E11 190
    E12 240
    H13 290
    H14 390
    FCW;
    FCW-PLA-GT
    592х490х292 6 M6 2800 70 14,0 5,4
    F7 80
    F8 90
    F9 110
    E10 160
    E11 190
    E12 240
    H13 290
    H14 390
    FCW;
    FCW-PLA-GT
    592х287х292 6 M6 1700 70 7,8 3,5
    F7 80
    F8 90
    F9 110
    E10 160
    E11 190
    E12 240
    H13 290
    H14 390
    FCW;
    FCW-PLA-GT
    592х592х420 6 M6 3400 40 25,0 11,5
    F7 50
    F8 70
    F9 85
    E10 130
    E11 150
    E12 200
    H13 250
    H14 350
    FCW;
    FCW-PLA-GT
    592х490х420 6 M6 2800 40 20,2 9,5
    F7 50
    F8 70
    F9 85
    E10 130
    E11 150
    E12 200
    H13 250
    Н14 350
    FCW;
    FCW-PLA-GT
    592х287х420 6 M6 1700 40 11,2 6,5
    F7 50
    F8 70
    F9 85
    E10 130
    E11 150
    E12 200
    H13 250
    H14 350

    Note:

    1.  Interstate Standard R EN 779 – 2014 for filtration classes M6; F7; F8; F9.
    2. Interstate Standard R EN 1822-1-2010 for filtration classes E10; E11; E12; H13; H14.

    Marking example:

    • FCW – PLA / F7 – 8 / 592 х 592 х 292 / NUP;
    • FCW – PLA – GT / F9 – 8 / 592 х 592 х 292 / NUP / S.

    Marking of compact W-shaped filters

     

    1 Type:

    • FCW – Compact W-shaped filter.

    2 Housing material:

    • PLA – plastic housing;
    • PLA-GT – plastic housing with protective grids (for energy and gas transportation industries).

    3 Filtration class according to:

    • Interstate Standard R EN 779-2014 – M5; M6; F7; F8; F9;
    • Interstate Standard R EN 1822-1-2010 – E10; E11; E12; H13; H14.

    4 Number of filter packs:

    • 6 pcs;
    • 8 pcs.

    5 Filter dimensions:

    • W – filter width (592 mm);
    • H – filter height (592; 490; 287 mm);
    • D – filter depth (292; 420 mm).

    6 Presence of sealant:

    • NV – continuous sealant on the air flow inlet side;
    • NP – continuous sealant on the air flow outlet side;
    • ND – continuous sealant on both sides.

    7 Testing:

    • ST – Test to determine the initial efficiency of a non-dusty filter for 0.4 μm. Differential test – determination of pressure drop as a function of clean filter air flow.

    Marking example:

    • FCW – PLA / F7 – 8 / 592 х 592 х 292 / NUP;
    • FCW – PLA – GT / F9 – 8 / 592 х 592 х 292 / NUP / S.